| TECHNICAL SPECIFICATIONS FOR SINGLE CORE, UNSHEATHED CABLES |
| Conductor nominal area n sq. mm. | Number & nominal dia.of wire No. /mm | Resistance (Max.) per km. @ 20°C in Ohms | Approximate over all dia. In mm | Current carrying capacity Two cables, single phase | Nominal thickness of insulation in mm | Approximate gross weight in kgs. |
| In conduit/ trunking inAmps. | Unenclosed-clipppeddirectly to a surface or on cable tray in Amps |
0.50 0.75 1.0 1.5 2.5 4.0 6.0 10.0 16.0 | 16/0.2** 24/0.2** 14/0.3* 22/0.3* 36/0.3* 56/0.3** 84/0.3** 140/0.3** 224/0.3** | 39.0 26.0 18.10 12.10 7.41 4.95 3.30 1.19 1.21 | 2.16 2.36 2.8 3.1 3.6 4.2 5.2 6.8 8.3 | 3 6 11 13 18 24 31 42 57 | 4 7 12 16 22 29 37 51 68 | 0.6 0.6 0.7 0.7 0.8 0.8 0.8 1.0 1.0 | 0.80 1.00 1.45 2.15 3.00 4.50 6.45 12.00# 18.00# |